320
PLC Setup Section 7-1
Input Time Constant Setting for the General-purpose Inputs
7-1-2-12 Origin Search Function
The following tables show the settings for the origin search function in the CX-
Programmer. These settings are for CJ1M CPU Units equipped with the built-
in I/O functions.
Note In the CX-Programmer version 3.1 or lower, the Tab Page's name is Define
Origin Operation Settings Field of Define Origin.
Programming
Console
address
Settings Default Function Related
Auxiliary
Area flags/
bits
Time when
setting is read
by CPU Unit
Word Bits
+61 00 to 07 00 hex: Default
(8 ms)
10 hex: 0 ms
(no filter)
11 hex: 0.5 ms
12 hex: 1 ms
13 hex: 2 ms
14 hex: 4 ms
15 hex: 8 ms
16 hex: 16 ms
17 hex: 32 ms
0 hex Specifies the input time constant for
general-purpose inputs IN0 to IN9.
Note This setting has no effect on
inputs set as interrupt inputs,
quick-response inputs, or
high-speed counters.
--- When operation
starts