PLC Setup Section 7-1
Detect Interrupt Task Error
Stop CPU on Instruction Error (Instruction Error Operation)
Do Not Register FAL to Error Log
Note This setting does not exists in CJ1@-CPU@@ CPU Units.
Memory Allocation Settings
EM File Setting Enabled
Note This setting does not exist in CJ1M CPU Units.
Programming
Console address
Settings Function Related
flags and
words
When set-
ting is read
by CPU Unit
Word Bit(s)
+128 14 0: Detect
1: Do not detect
Default: 0
This setting determines whether interrupt
task errors are detected. If this setting is set
to 0 and an interrupt task error is detected,
the ERR/ALM indicator on the CPU Unit will
flash and the Interrupt Task Error Flag
(A40213) will be turned ON, but CPU Unit
operation will continue.
A40213
(Interrupt
Task Error
Flag)
At the next
cycle.
Programming
Console address
Settings Function Related
flags and
words
When set-
ting is read
by CPU Unit
Word Bit(s)
+197 15 0: Continue
1: Stop
Default: 0
This setting determines whether instruction
errors (instruction processing errors (ER)
and illegal access errors (AER)) are treated
as non-fatal or fatal errors. When this setting
is set to 1, CPU Unit operation will be
stopped if the ER or AER Flags is turned
ON (even when the AER Flag is turned ON
for an indirect DM/EM BCD error).
Related Flags: A29508 (Instruction Pro-
cessing Error Flag)
A29509 (Indirect DM/EM BCD Error Flag)
A29510 (Illegal Access Error Flag)
A29508,
A29509,
A29510
(If this setting
is set to 0,
these flags
won’t be
turned ON
even if an
instruction
error occurs.)
At start of
operation.
Programming
Console address
Settings Function Related
flags and
words
When set-
ting is read
by CPU Unit
Word Bit(s)
+129 15 0: Record user-
defined FAL errors
in error log.
1: Don’t record user-
defined FAL errors
in error log.
Default: 0
This setting determines if user-defined FAL
errors created with FAL(006) and time moni-
toring for FPD(269) will be recorded in the
error log (A100 to A199). Set it to 1 so pre-
vent these errors from being recorded.
--- Whenever
FAL(006) is
executed
(every cycle).
Programming
Console address
Settings Function Related
flags and
words
When set-
ting is read
by CPU Unit
Word Bit(s)
+136 7 0: None
1: EM File Memory
Enabled.
Default: 0
This setting determines whether part of the
EM Area will be used for file memory.
--- After initial-
ization from
Program-
ming Device
or via FINS
command.