292
PLC Setup Section 7-1
EM Start File No.
Note This setting does not exist in CJ1M CPU Units.
Background Execution Settings
Table Data Process Instructions
Note This setting does not exists in CJ1@-CPU@@ CPU Units.
String Data Process Instructions
Note This setting does not exists in CJ1@-CPU@@ CPU Units.
Data Shift Process Instructions
Note This setting does not exists in CJ1@-CPU@@ CPU Units.
Programming
Console address
Settings Function Related
flags and
words
When set-
ting is read
by CPU Unit
Word Bit(s)
+136 0 to 3 0 to 6
Default: 0
If bit 7 (above) is set to 1, the setting here
specifies the EM bank where file memory
begins. The specified EM bank and all sub-
sequent banks will be used as file memory.
This setting will be disabled if bit 7 is set to
0.
A344 (EM
File Memory
Starting
Bank)
After initial-
ization from
Program-
ming Device
or via FINS
command.
Programming
Console address
Settings Function Related
flags and
words
When set-
ting is read
by CPU Unit
Word Bit(s)
+198 15 0: Not executed in
background.
1: Executed in back-
ground.
Default: 0
This setting determines if Table Data
Instructions will be processed over multiple
cycle times (i.e., processed in the back-
ground).
--- At start of
operation
Programming
Console address
Settings Function Related
flags and
words
When set-
ting is read
by CPU Unit
Word Bit(s)
+198 14 0: Not executed in
background.
1: Executed in back-
ground.
Default: 0
This setting determines if Text String Data
Instructions will be processed over multiple
cycle times (i.e., processed in the back-
ground).
--- At start of
operation
Programming
Console address
Settings Function Related
flags and
words
When set-
ting is read
by CPU Unit
Word Bit(s)
+198 13 0: Not executed in
background.
1: Executed in back-
ground.
Default: 0
This setting determines if Data Shift Instruc-
tions will be processed over multiple cycle
times (i.e., processed in the background).
--- At start of
operation