EasyManua.ls Logo

Omron CJ - 08-2008 - Page 128

Omron CJ - 08-2008
733 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
80
Specifications Section 2-1
Maximum number of
Expansion Racks
CJ1-H and CJ1 CPU Units:
3 max. (An I/O Control Unit is required on the CPU Rack and an I/O
Interface Unit is required on each Expansion Rack.)
CJ1M CPU Units (CPU 13/23 only):
1 max. (An I/O Control Unit is required on the CPU Rack and an I/O
Interface Unit is required on the Expansion Rack.)
CJ1M CPU Units (CPU11/12/21/22):
Expansion is not possible.
2-3-3 CJ-series Expan-
sion Racks
Number of tasks 288 (cyclic tasks: 32, interrupt tasks: 256)
With CJ1-H or CJ1M CPU Units, interrupt tasks can be defined as
cyclic tasks called “extra cyclic tasks.” Including these, up to 288 cyclic
tasks can be used.
Note 1 Cyclic tasks are executed each cycle and are controlled with
TKON(820) and TKOF(821) instructions.
Note 2 The following 4 types of interrupt tasks are supported.
Power OFF interrupt tasks: 1 max.
Scheduled interrupt tasks: 2 max.
I/O interrupt tasks: 32 max.
External interrupt tasks: 256 max.
Programming Manual:
1-3 Programs and
Ta sk s
Programming Manual:
SECTION 4: Tasks
Interrupt types Scheduled Interrupts:
Interrupts generated at a time scheduled by the CPU Units built-in
timer. (See note. 1)
I/O Interrupts:
Interrupts from Interrupt Input Units.
Power OFF Interrupts (See note 2.):
Interrupts executed when the CPU Unit’s power is turned OFF.
External I/O Interrupts:
Interrupts from the Special I/O Units or CPU Bus Units.
Note 1 CJ1-H and CJ1 CPU Units: Scheduled interrupt time interval
is either 1 ms to 9,999 ms (in increments of 1 ms) or 10 ms to
99,990 ms (in increments of 10 ms)
CJ1-H-R CPU Units: Scheduled interrupt time interval is
0.2 ms to 999.9 ms (in increments of 0.1 ms), 1 ms to 9,999
ms (in increments of 1 ms), or 10 ms to 99,990 ms (in incre-
ments of 10 ms)
CJ1M CPU Units: Scheduled interrupt time interval is 0.5 ms
to 999.9 ms (in increments of 0.1 ms), 1 ms to 9,999 ms (in
increments of 1 ms), or 10 ms to 99,990 ms (in increments of
10 ms)
Note 2 Not supported when the CJ1W-PD022 Power Supply Unit is
mounted.
Programming Manual:
4-3 Interrupt Tasks
Calling subroutines
from more than one
task
CJ1-H CPU Units: Supported (called “global subroutines”).
CJ1 CPU Units: Not supported.
Tasks: Programming
Manual (W394)
Function blocks (CPU
Unit with unit version
3.0 or later only)
Languages in function block definitions: ladder programming, struc-
tured text
Refer to the CX-Pro-
grammer Operation
Manual Function Blocks
(W438).
Item Specifications Reference

Table of Contents

Related product manuals