PLC Setup Section 7-1
Scheduled Interrupt Interval
Note CJ1M/CJ1-H-R CPU Units only.
Power OFF Detection Time (Power OFF Detection Delay Time) (See note.)
Note This setting is not supported when the CJ1W-PD022 Power Supply Unit is
mounted. (Refer to
Power OFF Operation on page 451.)
Power OFF Interrupt Disable (See note.)
Note This setting is not supported when the CJ1W-PD022 Power Supply Unit is
mounted. (Refer to
Power OFF Operation on page 451.)
Programming
Console address
Settings Function Related
flags and
words
When set-
ting is read
by CPU Unit
Word Bit(s)
+195 0 to 3 0: 10 ms
1: 1.0 ms
2: 0.1 ms (See
note.)
Default: 0
This setting determines the time units used
in scheduled interrupt interval settings.
(This setting cannot be changed during
operation.)
--- At start of
operation.
Programming
Console address
Settings Function Related
flags and
words
When set-
ting is read
by CPU Unit
Word Bit(s)
+225 0 to 7 00 to 0A:
0 to 10 ms
(1-ms units)
Default: 00
This setting determines how much of a
delay there will be from the detection of a
power interruption (approximately 10 to
25 ms for AC power and 2 to 5 ms for DC
power after the power supply voltage drops
below 85% of the rated value) to the confir-
mation of a power interruption. The default
setting is 0 ms.
When the power OFF interrupt task is
enabled, it will be executed when the power
interruption is confirmed. If the power OFF
interrupt task is disabled, the CPU will be
reset and operation will be stopped.
--- At startup or
at start of
operation.
(Can’t be
changed dur-
ing opera-
tion.)
Programming
Console address
Settings Function Related
flags and
words
When set-
ting is read
by CPU Unit
Word Bit(s)
+225 15 0: Disabled
1: Enabled
Default: 0
When this setting is set to 1, the power OFF
interrupt task will be executed when power
is interrupted.
--- At startup or
at start of
operation.
(Can’t be
changed dur-
ing opera-
tion.)