316
PLC Setup Section 7-1
High-speed Counter 0 Reset Method
High-speed Counter 0 Counting Mode
High-speed Counter 0 Circular Max. Count (Ring Counter Maximum Value)
Note When the CX-Programmer is being used to make the setting, the setting is
input in decimal.
Programming
Console
address
Settings Default Function Related
Auxiliary
Area flags/
bits
Time when
setting is read
by CPU Unit
Word Bits
+50 04 to 07 0 hex: Z phase,
software reset
(stop comparing)
1 hex: Software
reset (stop com-
paring)
2 hex: Z phase,
software reset
(continue com-
paring)
3 hex: Software
reset (continue
comparing)
0 hex Specifies the reset method for high-
speed counter 0.
--- When power is
turned ON
Programming
Console
address
Settings Default Function Related
Auxiliary
Area flags/
bits
Time when
setting is read
by CPU Unit
Word Bits
+50 08 to 11 0 hex:
Linear mode
1 hex:
Ring mode
0 hex Specifies the counting mode for high-
speed counter 0.
--- When operation
starts
Programming
Console
address
Settings Default Function Related
Auxiliary
Area flags/
bits
Time when
setting is read
by CPU Unit
Word Bits
+51 00 to 15 00000000 to
FFFFFFFF hex
(See note.)
00000000
hex
Sets the max. ring count for high-
speed counter 0.
When the high-speed counter 0
counting mode is set to ring mode,
the count will be reset to 0 automati-
cally when the counter PV exceeds
the max. ring count.
A270
(Rightmost 4
digits of the
high-speed
counter 0
PV)
When operation
starts
+52 00 to 15 A271
(Leftmost 4
digits of the
high-speed
counter 0
PV)