EasyManua.ls Logo

Omron CJ - 08-2008 - Page 374

Omron CJ - 08-2008
733 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
326
PLC Setup Section 7-1
Pulse Output 1 Origin Detection Method
Pulse Output 1 Origin Search Direction Setting
Pulse Output 1 Origin Search/Return Initial Speed
Note When the CX-Programmer is being used to make the setting, the setting is
input in decimal.
Pulse Output 1 Origin Search High Speed
Note When the CX-Programmer is being used to make the setting, the setting is
input in decimal.
Pulse Output 1 Origin Search Proximity Speed
Programming
Console
address
Settings Default Function Related
Auxiliary
Area flags/
bits
Time when
setting is read
by CPU Unit
Word Bits
+275 08 to 11 0 hex: Method 0
(Origin detection
method 0)
1 hex: Method 1
(Origin detection
method 1)
2 hex: Method 2
(Origin detection
method 2)
0 hex Specifies the origin detection method
for pulse output 1.
--- When operation
starts
Programming
Console
address
Settings Default Function Related
Auxiliary
Area flags/
bits
Time when
setting is read
by CPU Unit
Word Bits
+275 12 to 15 0 hex: CW direc-
tion
1 hex: CCW
direction
0 hex Specifies the origin search direction
for pulse output 1.
--- When operation
starts
Programming
Console
address
Settings Default Function Related
Auxiliary
Area flags/
bits
Time when
setting is read
by CPU Unit
Word Bits
+276 00 to 15 00000000 to
000186A0 hex
(See note.)
00000000
hex
Specifies the starting speed (0 to
100,000 pps) for the pulse output 1
origin search and origin return opera-
tions.
--- When operation
starts
+277 00 to 15
Programming
Console
address
Settings Default Function Related
Auxiliary
Area flags/
bits
Time when
setting is read
by CPU Unit
Word Bits
+278 00 to 15 00000001 to
000186A0 hex
(See note.)
000000
01 hex
Specifies the high speed setting (1 to
100,000 pps) for pulse output 1 origin
search operation.
--- When operation
starts
+279 00 to 15
Programming
Console
address
Settings Default Function Related
Auxiliary
Area flags/
bits
Time when
setting is read
by CPU Unit
Word Bits
+280 00 to 15 00000001 to
000186A0 hex
(See note.)
000000
00 hex
Specifies the proximity speed setting
(1 to 100,000 pps) for pulse output 1
origin search operation.
--- When operation
starts
+281 00 to 15

Table of Contents

Related product manuals