Auxiliary Area Section 9-11
■ Power Supply ON/OFF Time Information
Name Address Description Access
Startup Time A510 and
A511
These words contain the time (in BCD) at which the power
was turned ON. The contents are updated every time that
the power is turned ON.
A51000 to A51007: Seconds (00 to 59)
A51008 to A51015: Minutes (00 to 59)
A51100 to A51107: Hour (00 to 23)
A51108 to A51115: Day of the month (01 to 31)
Read/write
Power Interruption Time A512 and
A513
These words contain the time (in BCD) at which the power
was interrupted. The contents are updated every time that
the power is interrupted.
A51200 to A51207: Seconds (00 to 59)
A51208 to A51215: Minutes (00 to 59)
A51300 to A51307: Hour (00 to 23)
A51308 to A51315: Day of month (01 to 31)
Read/write
Number of Power
Interruptions
A514 Contains the number of times (in binary) that power has
been interrupted since the power was first turned on. To
reset this value, overwrite the current value with 0000.
Read/write
Total Power ON Time A523 Contains the total time (in binary) that the PLC has been on
in 10-hour units. The data is stored is updated every 10
hours. To reset this value, overwrite the current value with
0000.
Read/write
Power ON Clock Data 1 A720 to
A722
These words contain the startup date/time (the same time
as the startup time stored in words A510 to A511 as well as
the month and year information) for the last time that power
was turned ON. The data is BCD.
A72000 to A72007: Seconds (00 to 59)
A72008 to A72015: Minutes (00 to 59)
A72100 to A72107: Hour (00 to 23)
A72108 to A72115: Day of month (01 to 31)
A72200 to A72207: Month (01 to 12)
A72208 to A72215: Year (00 to 99)
Read/write