Auxiliary Area Section 9-11
Auxiliary Area Flags and Bits for Built-in Outputs
The following tables show the Auxiliary Area words and bits that are related to
the CJ1M CPU Unit's built-in outputs. These allocations apply to CPU Units
equipped with the built-in I/O only.
High-speed Counter
1
Count Direction
A27510 This flag indicates whether the high-speed
counter is currently being incremented or decre-
mented. The counter PV for the current cycle is
compared with the PV in last cycle to determine
the direction.
0: Decrementing
1: Incrementing
Read only Setting used for
high-speed
counter, valid dur-
ing counter opera-
tion.
High-speed Counter
0 Reset Bit
A53100 When the reset method is set to Phase-Z signal
+ Software reset, the corresponding high-speed
counter's PV will be reset if the phase-Z signal is
received while this bit is ON.
When the reset method is set to Software reset,
the corresponding high-speed counter's PV will
be reset in the cycle when this bit goes from
OFF to ON.
Read/Write Cleared when
power is turned
ON.
High-speed Counter
1 Reset Bit
A53101 Read/Write
High-speed Counter
0 Gate Bit
A53102 When a counter's Gate Bit is ON, the counter's
PV will not be changed even if pulse inputs are
received for the counter.
When the bit is turned OFF again, counting will
restart and the high-speed counter's PV will be
refreshed.
When the reset method is set to Phase-Z signal
+ Software reset, the Gate Bit is disabled while
the corresponding Reset Bit (A53100 or
A53101) is ON.
Read/Write Cleared when
power is turned
ON.
High-speed Counter
1 Gate Bit
A53103 Read/Write
Name Address Description Read/Write Times when data is
accessed
Name Address Description Read/Write Times when data is
accessed
Pulse Output 0 PV A276 to
A277
Contain the number of pulses output from the
corresponding pulse output port.
PV range: 80000000 to 7FFFFFFF hex
(2,147,483,648 to 2,147,483,647)
When pulses are being output in the CW direc-
tion, the PV is incremented by 1 for each pulse.
When pulses are being output in the CCW direc-
tion, the PV is decremented by 1 for each pulse.
PV after overflow: 7FFFFFFF hex
PV after underflow: 80000000 hex
A277 contains the leftmost 4 digits and A276
contains the rightmost 4 digits of the pulse out-
put 0 PV.
A279 contains the leftmost 4 digits and A278
contains the rightmost 4 digits of the pulse out-
put 1 PV.
Note If the coordinate system is relative coor-
dinates (undefined origin), the PV will be
cleared to 0 when a pulse output starts,
i.e. when a pulse output instruction
(SPED(885), ACC(888), or PLS2(887)) is
executed.
Read only Cleared when
power is turned
ON.
Cleared when
operation starts.
Refreshed each
cycle during over-
see process.
Refreshed when
the INI(880)
instruction is exe-
cuted for the cor-
responding pulse
output.
Pulse Output 1 PV A278 to
A279