EasyManua.ls Logo

Omron CJ - 08-2008 - Page 558

Omron CJ - 08-2008
733 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
510
Error Processing Section 11-2
Program
error
(cont.)
PRO-
GRAM
ERR
80F0 A40109:
Program
Error Flag
A294 to
A299: Pro-
gram error
information
A29513: Differentiation over-
flow error
Too many differentiated
instructions have been
inserted or deleted during
online editing.
After writing any changes to the pro-
gram, switch to PROGRAM mode and
then return to MONITOR mode to con-
tinue editing the program.
A29512: Task error
A task error has occurred.
The following conditions will
generate a task error.
1) There isn’t an executable
cyclic task.
2) There isn’t a program allo-
cated to the task. Check
A294 for the number of the
task missing a program.
3) The task specified in a
TKON(820), TKOF(821), or
MSKS(690) instruction
doesn’t exist.
Check the startup cyclic task attributes.
Check the execution status of each task
as controlled by TKON(820) and
TKOF(821).
Make sure that all of the task numbers
specified in TKON(820), TKOF(821),
and MSKS(690) instructions have corre-
sponding tasks.
Use MSKS(690) to mask any I/O or
scheduled interrupt tasks that are not
being used and that do not have pro-
grams set for them.
A29510: Illegal access error
An illegal access error has
occurred and the PLC Setup
has been set to stop opera-
tion for an instruction error.
The following are illegal
access errors:
1. Reading/writing a parame-
ter area.
2. Writing memory that is not
installed.
3. Writing an EM bank that is
EM file memory.
4. Writing to a read-only area.
5. Indirect DM/EM address
that is not in BCD when BCD
mode is specified.
Find the program address where the
error occurred (A298/A299) and correct
the instruction.
A29509: Indirect DM/EM
BCD error
An indirect DM/EM BCD error
has occurred and the PLC
Setup has been set to stop
operation for an instruction
error.
Find the program address where the
error occurred (A298/A299) and correct
the indirect addressing or change to
binary mode.
A29508: Instruction error
An instruction processing
error has occurred and the
PLC Setup has been set to
stop operation for an instruc-
tion error.
Find the program address where the
error occurred (A298/A299) and correct
the instruction.
A29514: Illegal instruction
error
The program contains an
instruction that cannot be
executed.
Retransfer the program to the CPU Unit.
Error Program-
ming
Console
display
Error
code (in
A400)
Flag and
word data
Probable cause Possible remedy

Table of Contents