580
Specifications of Basic I/O Units Appendix A
When overcurrent is detected, the ERR indicator will light, and the corresponding flag in the Basic I/O Unit
Information Area (A050 to A069) will turn ON.
Terminal Connections
When wiring, pay careful attention to the polarity of the external power supply. The load may operate if the
polarity is reversed.
Note Terminal numbers A0 to A9 and B0 to B9 are used in this manual, but they are not printed on the Unit.
CJ1W-OD212 Transistor Output Unit (Terminal Block, 16 Points,
Sourcing)
B1
1
B2
3
B3
5
B4
7
B5
B6
B7
B8
24 V DC
A1
0
A2
2
A3
4
A4
6
A5
NC
A6
A7
A8
0 V
B0
A0
COM(+V)
L
L
L
L
L
L
L
L
NC
NC
NC
NC
NC
NC
NC
Rated Voltage 24 V DC
Operating Load Voltage Range 20.4 to 26.4 V DC
Maximum Load Current 0.5 A/point, 5.0 A/Unit
Maximum Inrush Current 0.1 mA max.
Leakage Current 1.5 V max.
ON Response Time 0.5 ms max.
OFF Response Time 1.0 ms max.
Load Short-circuit Prevention Detection current: 0.7 to 2.5 A
Automatic restart after error clearance. (Refer to
page 590.)
Insulation Resistance 20 MΩ between the external terminals and the GR
terminal (100 V DC)
Dielectric Strength 1,000 V AC between the external terminals and the
GR terminal for 1 minute at a leakage current of
10 mA max.
Number of Circuits 16 (16 points/common, 1 circuits)
Internal Current Consumption 5 V DC, 100 mA max.
External Power Supply 20.4 to 26.4 V DC, 40 mA min.
Weight 120 g max.