632
Auxiliary Area Appendix C
The following data would be generated in an error record if a memory error (error code 80F1) occurred on 1
April 1998 at 17:10:30 with the error located in the PLC Setup (04 hex).
The following data would be generated in an error record if an FALS error with FALS number 001 occurred on
2 May 1997 at 8:30:15.
Error Codes and Error Flags
Note 1. C101 to C2FF will be stored for FALS numbers 001 to 511.
2. 4101 to 42FF will be stored for FAL numbers 001 to 511.
3. The contents of the error flags for a duplicate number error are as follows:
Bits 0 to 7: Unit number (binary), 00 to 5F hex for Special I/O Units, 00 to 0F hex for CPU Bus Units
Bits 8 to 14: All zeros.
Bit 15: Unit type, 0 for CPU Bus Units and 1 for Special I/O Units.
4. Only the contents of A295 is stored as the error flag contents for program errors.
5. 0000 hex will be stored as the error flag contents.
Classification Error code Meaning Error flags
System-defined
fatal errors
80F1 Memory error A403
80C0 to 80C7
80CE, 80CF
I/O bus error A404
80E9 Duplicate number error A410, A411 to 416 (See note 3.)
80E1 Too many I/O error A407
80E0 I/O setting error ---
80F0 Program error A295 to 299 (See note 4.)
809F Cycle time too long error ---
80EA Duplicate Expansion Rack number error A40900 to 40907
User-defined
fatal errors
C101 to C2FF FALS instruction executed (See note 1.) ---
User-defined
non-fatal errors
4101 to 42FF FAL instruction executed (See note 2.) ---
System-defined
non-fatal errors
008B Interrupt task error A426
009A Basic I/O error A408
009B PLC Setup setting error A406
0200 to 020F CPU Bus Unit error A417
0300 to 035F Special I/O Unit error A418 to 423 (See note 5.)
00F7 Battery error ---
0400 to 040F CPU Bus Unit setup error A427
0500 to 055F Special I/O Unit setup error A428 to 433 (See note 5.)