PLC Setup Coding Sheets for Programming Console Appendix E
Built-in Inputs IN0 to IN3 Operation Settings
Input Time Constant Setting for General-purpose Inputs
Value (hex) IN0 operation settings
A 0 Normal (General-purpose inputs)
1 Interrupt (Interrupt inputs)
2 Quick (Quick-response inputs
Value (hex) IN1 operation settings
B Same as for IN0.
Value (hex) IN2 operation settings
C Same as for IN0.
Value (hex) IN3 operation settings
D Same as for IN0.
Value (hex) Input time constant
A 0000 Default (8 ms)
0010 0 ms (No filter)
0011 0.5 ms
0012 1 ms
0013 2 ms
0014 4 ms
0015 8 ms
0016 16 ms
0017 32 ms
Value (hex) IOM Hold Bit Status at
Startup
Forced Status Hold Bit
Status at Startup
A C000 Retained Retained
8000 Retained Cleared
4000 Cleared Retained
0000 Cleared Cleared