PLC Setup Coding Sheets for Programming Console Appendix E
RS-232C Port
RS-232C Port
Note Set 0000 to 0009 hex for standard NT Link and 000A hex for high-
speed NT Link. Set 0000 hex for standard Serial PLC Link and 000A
hex for high-speed Serial PLC Link.
160@@@@
A
B
Address
Value (hex) Data bits Stop bits Parity
A 00 7 bits 2 bits Even
01 7 bits 2 bits Odd
02 7 bits 2 bits None
04 7 bits 1 bit Even
05 7 bits 1 bit Odd
06 7 bits 1 bit None
08 8 bits 2 bits Even
09 8 bits 2 bits Odd
0A 8 bits 2 bits None
0C 8 bits 1 bit Even
0D 8 bits 1 bit Odd
0E 8 bits 1 bit None
Value (hex) Communications mode
B 00 Default (Rightmost 2 digits ignored.)
80 Host link
82 NT link
83 No-protocol
84 Peripheral bus
85 Host link
87 Serial PLC Link Polled Unit
88 Serial PLC Link Polling Unit