EasyManuals Logo

Omron CPM1 Programming Manual

Omron CPM1
541 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #287 background imageLoading...
Page #287 background image
266
Conversion Instructions Section 5-19
Any or all of the digits in S may be converted in sequence from the designated
first digit. The first digit, the number of digits to be converted, and the half of D
to receive the first 7-segment display code (rightmost or leftmost 8 bits) are
designated in Di. If multiple digits are designated, they will be placed in order
starting from the designated half of D, each requiring two digits. If more digits
are designated than remain in S (counting from the designated first digit), fur-
ther digits will be used starting back at the beginning of S.
Digit Designator The digits of Di are set as shown below.
Some example Di values and the 4-bit binary to 7-segment display conver-
sions that they produce are shown below.
Specifies the first digit of S to be converted (0 to 3).
Number of digits to be converted (0 to 3)
0: 1 digit
1: 2 digits
2: 3 digits
3: 4 digits
First half of D to be used.
0: Rightmost 8 bits (1st half)
1: Leftmost 8 bits (2nd half)
Not used; set to 0.
Digit number: 3 2 1 0
0
1
2
3
0
1
2
3
S digits
Di: 0011
D
Di: 0030
S digits
0
1
2
3
Di: 0130
S digits
Di: 0112
0
1
2
3
S digits
1st half
2nd half
D
1st half
2nd half
D+1
1st half
2nd half
D
1st half
2nd half
D+1
1st half
2nd half
D
1st half
2nd half
D+1
1st half
2nd half
D+2
1st half
2nd half

Table of Contents

Other manuals for Omron CPM1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CPM1 and is the answer not in the manual?

Omron CPM1 Specifications

General IconGeneral
ModelCPM1
ManufacturerOmron
Instruction SetBasic and advanced instructions
Power Supply100 to 240 VAC or 24 VDC
CommunicationRS-232C
I/O Points10, 20, 30, or 40 points depending on the model
TimersYes, multiple timers available
CountersYes, multiple counters available
Input Voltage24V DC
Output TypeRelay or transistor
Number of I/O Points10, 20, 30, 40
Communication PortsRS-232C (optional)
Operating Temperature0°C to 55°C
Storage Temperature-20°C
Humidity10% to 90% (non-condensing)
DimensionsVaries depending on the model
WeightVaries depending on the model
Program Memory2048 steps (2K steps)