EasyManua.ls Logo

Omron NX-EIC202 - Section 7 Wiring; Ethernet;Ip Network Wiring; Installation Precautions; Preparations for Installation

Omron NX-EIC202
430 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7 Wiring
7 - 2
NX-series EtherNet/IP Coupler Unit User’s Manual (W536)
7-1 EtherNet/IP Network Wiring
This section describes how to install the EtherNet/IP network.
Basic precautions for the installation of EtherNet/IP networks are provided below.
When you install an EtherNet/IP network, take sufficient safety precautions and perform the installa-
tion according to all applicable standards and specifications. An expert well versed in safety mea-
sures and the standards and specifications should be asked to perform the installation.
Do not install EtherNet/IP network equipment near sources of noise.
If the network must be installed in an area with noise, take steps to address the noise, such as plac-
ing equipment in metal cases.
Check the following items on the communications cables that are used in the network.
Are there any breaks?
Are there any shorts?
Are there any connector problems?
When you connect the cable to the communications connectors on devices, firmly insert the commu-
nications cable connector until it locks in place.
Do not lay the communications cables together with high-voltage lines.
Do not lay the communications cable near devices that generate noise.
Do not lay the communications cables in locations subject to high temperatures or high humidity.
Do not lay the communications cables in locations subject to excessive dust, oil mist, or other con-
taminants.
There are limitations on the bending radius of communications cables. Check the specifications of
the communications cable for the bending radius.
Prepare the following devices.
7-1-1 Installation Precautions
Precautions when Installing a Network
Precautions when Installing Communications Cables
7-1-2 Preparations for Installation
Product Remarks
Twisted-pair cable The twisted-pair cable connects EtherNet/IP Units or built-in Ether-
Net/IP ports to the Ethernet switch, with an RJ45 Modular Connector at
each end.
Use an STP (shielded twisted-pair) cable of category 5 or higher.