A-8-4 Objects That Accept I/O Allocations
These objects accept I/O allocations.
Refer to Allocatable I/O Data in an EtherNet/IP Coupler Unit on page 9-13 under 9-2-3 I/O Allocation
Information on page 9-12 for details on the data for objects that allow I/O allocations.
Subindexes 01 to 03 hex tell whether the NX Unit is registered in the Unit configuration information.
Subindexes 01 to 03 tell whether the message communications are enabled in the NX Units.
A-8-4 Objects That Accept I/O Allocations
Index
(hex)
Subin-
dex
(hex)
Object name Default Data range Unit Data type Access
I/O
allo-
cat-
ion
Data
attri-
bute
2003 --- NX Unit Registration
Status
--- --- --- --- --- --- ---
00 Number of Entries 3 3 --- USINT RO Not
pos-
sible.
---
01 NX Unit Registration
Status 15
FALSE FALSE or
TRUE
--- ARRAY
[0..15] OF
BOOL
RO Pos-
sible.
---
02 NX Unit Registration
Status 31
FALSE FALSE or
TRUE
--- ARRAY
[0..31] OF
BOOL
RO Pos-
sible.
---
03 NX Unit Registration
Status 63
FALSE FALSE or
TRUE
--- ARRAY
[0..63] OF
BOOL
RO Pos-
sible.
---
Index
(hex)
Subin-
dex
(hex)
Object name Default Data range Unit Data type Access
I/O
allo-
cat-
ion
Data
attri-
bute
2004 --- NX Unit Message
Enabled Status
--- --- --- --- --- --- ---
00 Number of Entries 3 3 --- USINT RO Not
pos-
sible.
---
01 NX Unit Message
Enabled Status 15
FALSE FALSE or
TRUE
--- ARRAY
[0..15] OF
BOOL
RO Pos-
sible.
---
02 NX Unit Message
Enabled Status 31
FALSE FALSE or
TRUE
--- ARRAY
[0..31] OF
BOOL
RO Pos-
sible.
---
03 NX Unit Message
Enabled Status 63
FALSE FALSE or
TRUE
--- ARRAY
[0..63] OF
BOOL
RO Pos-
sible.
---