12 Troubleshooting
12 - 32
NX-series EtherNet/IP Coupler Unit User’s Manual (W536)
Event name Unit Configuration Information Error Event code 35000000 hex
Meaning An error occurred in the Unit configuration information in the Communications Coupler Unit.
Source EtherNet/IP Source details EtherNet/IP
Coupler Unit
Detection
timing
When power is
turned ON to
the EtherNet/IP
Coupler Unit or
the Slave Ter-
minal is
restarted
Error
attributes
Level Minor fault Recovery Cycle power to
the EtherNet/IP
Coupler Unit or
restart the
Slave Terminal.
Log category System
Effects
User program
Continues. Operation EtherNet/IP Coupler Unit, EtherNet/IP Communi-
cations
Ethernet communication stops.
EtherNet/IP Coupler Unit, NX Bus
I/O refreshing for the NX Units in the Slave Termi-
nal stops.
Messages cannot be sent to the NX Units in the
Slave Terminal.
Sys-
tem-defined
variables
Variable Data type Name
None --- ---
Cause and
correction
Assumed cause Correction Prevention
The power supply to the Commu-
nications Coupler Unit was turned
OFF or Support Software commu-
nications were disconnected while
downloading the Unit configura-
tion information.
Clear all of memory in the Com-
munication Coupler Unit, and then
download the Unit configuration
information again.
Do not turn OFF the power supply
to the Communications Coupler
Unit or disconnect Support Soft-
ware communications while down-
loading the Unit configuration
information.
Attached
information
None
Precautions/
Remarks
None