12 - 41
12   Troubleshooting
NX-series EtherNet/IP Coupler Unit User’s Manual (W536)
12-3  Checking for Errors and Troubleshooting with Support Soft-
ware
12
12-3-5  Event Codes for Errors and Troubleshooting Procedures
Event name NX Unit Initialization Error Event code 84C10000 hex
Meaning Initializing an NX Unit failed.
Source EtherNet/IP Source details EtherNet/IP 
Coupler Unit
Detection 
timing
When power is 
turned ON to 
the EtherNet/IP 
Coupler Unit, 
the Slave Ter-
minal is 
restarted, an 
NX Unit is 
restarted, or an 
error is reset in 
the EtherNet/IP 
Coupler Unit
Error 
attributes
Level Minor fault Recovery Reset error in 
EtherNet/IP 
Coupler Unit.
Log category System
Effects
User program
Continues. Operation When Fail-soft Operation Is Set to Fail-soft
• EtherNet/IP Coupler Unit, NX Bus
I/O refreshing for all of the NX Units that have an 
initialization error in the Slave Terminal stops.
When Fail-soft Operation Is Set to Stop
• EtherNet/IP Coupler Unit, EtherNet/IP Communi-
cations
Ethernet communication stops.
• EtherNet/IP Coupler Unit, NX Bus
I/O refreshing for the NX Units in the Slave Termi-
nal stops.
Sys-
tem-defined 
variables
Variable Data type Name
None --- ---
Cause and 
correction
Assumed cause Correction Prevention
An error occurred in processing 
the Communication Coupler Unit.
Set and save the Unit configura-
tion information in the Communi-
cation Coupler Unit again.
If this error occurs again, check 
that there are no errors in the NX 
Unit settings and I/O data map-
ping information, and correct any 
errors that are found.
Correctly set NX Units and I/O 
data mapping information, and set 
and save the Unit configuration 
information in the Communication 
Coupler Unit.
An initialization error occurred in 
an NX Unit.
Cycle the power supply to the rel-
evant NX Unit.
If the error occurs again, replace 
the NX Unit.
None
The Channel Enable/Disable Set-
ting for all channels of the Analog 
Input Unit are set to Disable.
The Enabled Channel Settings for 
all channels of the Analog Output 
Unit are set to Disable.
Set the Enabled Channel Setting 
to Enable for at least one channel.
Set the Enabled Channel Setting 
to Disabled for only the unused 
channels.
Attached 
information
Attached information 1: Unit number of the NX Unit where the error was detected
Precautions/
Remarks
None