A - 63
Appendices
NX-series EtherNet/IP Coupler Unit Users Manual (W536)
A-8 NX Objects
A
A-8-4 Objects That Accept I/O Allocations
Subindex 01 hex gives the Slave Terminal error status, Error Detection Flag, and I/O Refresh Flag.
The assignments of bits for subindex 01 hex are listed below.
Bit 15: I/O Refresh Flag
Bit 14: Error Detection Flag
Bits 8 to 13: Reserved
Bit 7: Slave Terminal Major Fault
Bit 6: Slave Terminal Partial Fault
Bit 5: Slave Terminal Minor Fault
Bit 4: Slave Terminal Observation
Bits 0 to 3: Reserved
Bits 4 to 7 are 0 (FALSE) if no error exists or 1 (TRUE) if an error exists.
The Error Detection Flag in bit 14 is 1 (TRUE) if any of bits 4 to 7 are 1 (TRUE). Otherwise, it is 0
(FALSE).
The I/O Refresh Flag in bit 15 is 1 (TRUE) if I/O communications are active for all of the NX Units in
the Slave Terminal. Otherwise, it is 0 (FALSE).
Index
(hex)
Subin-
dex
(hex)
Object name Default Data range Unit Data type
Acc
ess
I/O
allo-
cat-
ion
Data
attri-
bute
2008 --- Slave Terminal Status --- --- --- --- --- --- ---
00 Number of Entries 1 1 --- USINT RO Not
pos-
sible.
---
01 Slave Terminal Status 0000 hex --- --- WORD RO Pos-
sible.
---
Reserved --- --- --- BIT4 RO Not
pos-
sible.
---
Slave Terminal Observa-
tion
FALSE FALSE or
TRUE
--- BOOL RO Pos-
sible.
---
Slave Terminal Minor
Fault
FALSE FALSE or
TRUE
--- BOOL RO Pos-
sible.
---
Slave Terminal Partial
Fault
FALSE FALSE or
TRUE
--- BOOL RO Pos-
sible.
---
Slave Terminal Major
Fault
FALSE FALSE or
TRUE
--- BOOL RO Pos-
sible.
---
Reserved --- --- --- BIT6 RO Not
pos-
sible.
---
Error Detection Flag FALSE FALSE or
TRUE
--- BOOL RO Pos-
sible.
---
I/O Refresh Flag FALSE FALSE or
TRUE
--- BOOL RO Pos-
sible.
---