7-26
D Input Terminal Status (Register 002B Hex)
Bit No. Function
0 Forward/stop terminal (S1) (1: ON)
1 Multi-function input terminal 1 (S2) (1: ON)
2 Multi-function input terminal 2 (S3) (1: ON)
3 Multi-function input terminal 3 (S1) (4: ON)
4 Multi-function input terminal 4 (S5) (1: ON)
5 to 15 Not used.
D Inverter Status 1 (Register 002C Hex)
Bit No. Function
0 During RUN (1: During RUN)
1 Zero speed (1: Zero speed)
2 Frequency agree (1: Frequency agree)
3 Warning (Nonfatal error) (1: Warning)
4
Frequency detection 1 (1: Output frequency x n58)
5
Frequency detection 2 (1: Output frequency y n58)
6 Inverter ready (1: Ready)
7 UV (1: UV)
8 Base block (1: Base block)
9 Frequency reference mode (1: Other than communications)
10 RUN command mode (1: Other than communications)
11 Overtorque detection (1: Overtorque detection)
12 Not used.
13 Fault retry (1: Fault retry)
14 Fault (1: Fault)
15 Communications time-over: No normal communications for 2 s or more
(1: Communications time-over detecting)
D Output Terminal Status (Register 002D Hex)
Bit No. Function
0 Multi-function contact output terminal MA (1: ON)
1 to 15 Not used.
D Communications Error (Register 003D Hex)
Bit No. Function
0 CRC error (1: Error)
1 Data length error (1: Error)
2 Not used.
3 Parity error (1: Error)
4 Overrun error (1: Error)
5 Framing error (1: Error)
6 Communications time-over (1: Error)
7 to 15 Not used.