7-52
Send Data: S
DM Area
D01000 000B (Number of send data items: 11) (See note 1.)
D01001 0003 (Number of Slaves)
D01002 0001 (Slave 1 address)
D01003 RUN command to Slave 1
D01004 Frequency reference to Slave 1
D01005 0002 (Slave 2 address)
D01006 RUN command to Slave 2
D01007 Frequency reference to Slave 2
D01008 0003 (Slave 3 address)
D01009 RUN command to Slave 3
D01010 Frequency reference to Slave 3
Recv data: D
DM Area
D02000 0003 (Number of Recv data items: 3) (See note 2.)
D02001 Slave 1 Inverter status
D02002 Slave 2 Inverter status
D02003 Slave 3 Inverter status
Note 1. Set the number of send data items in Hex to the number of words from D01000 to D01010
(11).
Note 2. The number of words from D02001 to D02003 (3) is written in Hex in the number of Recv data
items.
D Status Flags
Communications Port Enabled Flags
If communications port 7 is selected: A20207
Protocol Macro Execution Flag
The address of the Protocol Macro Execution Flag is as follows:
Model Port 1 Port 2
CS1 Communications Board 190915 191915
CS1 Communications Unit Bit 15 of word n+9 (See note.) Bit 15 of word n+19 (See note.)
Note n = 1500 + 25 × unit number
Communications Port Abort Flag
The address of the Communications Port Abort Flag is as follows:
Model Port 1 Port 2
CS1 Communications Board 190913 191913
CS1 Communications Unit Bit 13 of word n+9 (See note.) Bit 13 of word n+10 (See note.)
Note n = 1500 + 25 × unit number