10-2
Parame-
ter No.
(Register
No.
(Hex))
Name Description Setting
range
Unit of
setting
Default
setting
Changes
during op-
eration
Refer-
ence
page
n01
(0101)
Parameter
write-pro-
hibit selec-
tion/
parameter
initializa-
tion
Used to prohibit parameters to be written, sets
parameters, or change the monitor range of
parameters.
Used to initialize parameters to default values.
0: Sets or monitors parameter n01. Parame-
ters n02 through n79 can be monitored
only.
1: Sets or monitors parameters n01 through
n79.
5: Enables continuous operation. (Parameters
n01 to n79 can be set or monitored.)
6: Clears the error log.
8: Initializes parameters to default values in
2-wire sequence.
9: Initializes parameters to default values in
3-wire sequence.
Note With settings 0 or 1, operation com-
mands are ignored in Program Mode.
(Refer to 3-1-2 Drive Mode and Pro-
gram Mode.) Normally, use a setting of
0 or 1.
0, 1, 6, 8,
9
1 1 No 5-2
n02
(0102)
Operation
command
selection
Used to select the input method for the RUN
and STOP commands in remote mode.
0: The RUN and STOP/RESET Keys on the
Digital Operator are enabled.
1: Multi-function inputs through the control cir-
cuit terminals in 2- or 3-wire sequence.
2: Operation commands via RS-422/485 com-
munications are enabled.
Note The RUN command only through key
sequences on the Digital Operator is
acceptable in local mode.
0 to 2 1 0 No 5-7
n03
(0103)
Frequency
reference
selection
Used to set the input method for the frequency
reference in remote mode.
0: Digital Operator
1: Frequency reference 1 (n21)
2: Frequency reference control circuit terminal
(0 to 10 V)
3: Frequency reference control circuit terminal
(4 to 20 mA)
4: Frequency reference control circuit terminal
(0 to 20 mA)
6: Frequency reference via RS-422/485 com-
munications
0 to 4, 6 1 0 No 5-8
n04
(0104)
Interrup-
tion mode
selection
Used to set the stopping method for use when
the STOP command is input.
0: Decelerates to stop in preset time.
1: Coasts to stop (with output shut off by the
STOP command)
0, 1 1 0 No 5-17
n05
(0105)
Reverse
rotation-
prohibit
selection
Used to select the operation with the reverse
command input.
0: Reverse enabled.
1: Reverse disabled.
0, 1 1 0 No 5-16
List of Parameters Chapter 10

Table of Contents