10-6
Parame-
ter No.
(Register
No.
(Hex))
Name Description Setting
range
Unit of
setting
Default
setting
Changes
during
operation
Refer-
ence
page
n36
124
Multi-function
input 1 (Input
Used to select the functions of multi-function input
terminals S2 through S5.
2 to 8,
10 to
1 2 No 5-18
terminal S2)
Set
value
Function Description
22
n37
(0125)
Multi-function
input 2 (Input
terminal S3)
0 Forward/Re-
verse rotation
command
3-wire sequence (to be set
in n37 only)
By setting n37 to 0, the
set value in n36 is ignored
and the following setting
0, 2 to
8, 10 to
22
1 5 No 5-18
n38
(0126)
Multi-function
input 3 (Input
terminal S4)
are forcibly made.
S1: RUN input (RUN
when ON)
S2: STOP input (STOP
when OFF)
-
2 to 8,
10 to
22
1 3 No 5-18
n39
0127
Multi-function
input 4 (Input
-
tion command (OFF: For-
ward; ON: Reverse)
2 to 8,
10 to
1 6 No 5-18
terminal S5)
2 Reverse/Stop Reverse rotation com-
mand in 2-wire sequence
(Reversed with the termi-
nal turned ON)
22, 34,
35
3 External fault
(NO)
ON: External fault (FPj
detection: j is a terminal
number)
4 External fault
(NC)
OFF: External fault (EFj
detection: j is a terminal
number)
5 Fault reset ON: Fault reset (disabled
while RUN command is in-
put)
6 Multi-step
speed refer-
ence 1
Signals to select frequen-
cy references 1 through 8.
-
-
-
7 Multi-step
speed refer-
ence 2
-
-
-
quency References
through Key Sequences
for the relationship be-
8 Multi-step
speed refer-
ence 3
tween multi-step speed
references and frequency
references.
10 Inching fre-
quency com-
mand
ON: Inching frequency
command (taking prece-
dence over the multi-step
speed reference)
11 Acceleration/
Deceleration
time change-
over
ON: Acceleration time 2
and deceleration time 2
are selected.
List of Parameters Chapter 10