Parker Hannifin
P Series User Guide 224
0x211C
Gain Conversion Waiting Time 1 ALL
e
Setting Range
Default
Value
Unit
Acces
sibility
Allocati
Change
Property
Stor
e
UINT 0 to 1000 0 ms RW Yes
Yes
Set the waiting time before conversion from gain group 1 to gain group 2.
0x211D
Gain Conversion Waiting Time 2 ALL
e
Setting Range
Default
Value
Unit
Acces
sibility
Allocati
Change
Property
Stor
e
UINT 0 to 1000 0 ms RW Yes
Yes
Set the waiting time before conversion from gain group 2 to gain group1.
0x211E
Dead Band for Position Control ALL
e
Setting Range
Default
Value
Unit
Acces
sibility
Allocati
Change
Property
Stor
e
UINT 0 to 1000 0 UU RW Yes
Yes
During position control, the position controller output becomes 0 if the following error for
position control is under the set value.
0x211F
Drive Control Input 1 ALL
e
Setting Range
Default
Value
Unit
Acces
sibility
Allocati
Change
Property
Stor
e
UINT 0 to 0xFFFF 0 - RW Yes
No
The signal to the input contact of the drive can be input by the signal input through the
I/O connector as well as by setting the bit corresponding to the input. In addition, the
relevant function is activated through logical OR calculation of the signal input through
the I/O connector and the bit value under this setting.
Please see the table below for input descriptions