Parker Hannifin
P Series User Guide 42
B. Regeneration brake resistor setting (0x2009)
- Select the built-in regeneration brake (0x2009 = 0)
- Attach to the backside of the heat protection panel
- Default value: 0
C. Check the internal regeneration brake value and power
- Check internal regeneration brake value (0x200B)
- Check regeneration brake power (0x200C)
- 1KW or less : Attach to the backside of the heat protection panel(See the
figure below)
- 3.5KW ~ 15KW : install inside the drive
- 15KW or above: no internal regeneration brake