If there are only 2416 modules on the PAMIO
rack, the maximum number of I/Os is:
As an example with a control unit PA 8000 LW
with analog axes:
N
Build-In
= 3 (one axis module and two I/O modules)
=> Max. number of PAMIO 2416: N
2416
= 28
Max. number of digital I/Os:
– 28 x 24 Inputs = 672 inputs + (build-in inputs) =
720 inputs
– 28 x 16 Outputs = 448 outputs + (build-in out-
puts) = 480 inputs
If a system rack requires 1 box with 2 modules
4ENC4A and 1 box with 1 module PWM, the
maximum number of modules 2416 is:
N
2416
= 31 - N
Build-In
- N
4ENC4A
- N
PWM
N
2416
= 31 - N
Build-In
- 2 - 1
As an example with a control unit PA 8000 E2 with
SDI axes:
N
Build-In
= 2 (no axis module and two I/O modules)
=> Max. number of PAMIO 2416: N
2416
= 26
Max. number of digital I/Os:
– 26 x 24 Inputs = 624 inputs + (build-in inputs) =
672 inputs
– 26 x 16 Outputs = 416 outputs + (build-in out-
puts) = 448 inputs
Example 1
Example 2
PA 8000 PAMIO
PAMIO Components
12.01.2017 | 26