If there are only 2416 modules on the PAMIO
rack, the maximum number of I/Os is:
As an example with a control unit PA 8000 LW
with analog axes:
N
Build-In
= 3 (one axis module and two I/O modules)
=> Max. number of PAMIO 2416: N
2416
= 28
Max. number of digital I/Os:
28 x 24 Inputs = 672 inputs + (build-in inputs) =
720 inputs
28 x 16 Outputs = 448 outputs + (build-in out-
puts) = 480 inputs
If a system rack requires 1 box with 2 modules
4ENC4A and 1 box with 1 module PWM, the
maximum number of modules 2416 is:
N
2416
= 31 - N
Build-In
- N
4ENC4A
- N
PWM
N
2416
= 31 - N
Build-In
- 2 - 1
As an example with a control unit PA 8000 E2 with
SDI axes:
N
Build-In
= 2 (no axis module and two I/O modules)
=> Max. number of PAMIO 2416: N
2416
= 26
Max. number of digital I/Os:
26 x 24 Inputs = 624 inputs + (build-in inputs) =
672 inputs
26 x 16 Outputs = 416 outputs + (build-in out-
puts) = 448 inputs
Example 1
Example 2
PA 8000 PAMIO
PAMIO Components
12.01.2017 | 26

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the power automation PA 8000 and is the answer not in the manual?

power automation PA 8000 Specifications

General IconGeneral
Brandpower automation
ModelPA 8000
CategoryControl Unit
LanguageEnglish

Related product manuals