4.3.4 Ambient Conditions
Property Value Unit
Operating tempera-
ture
+5 - +55 °C
+32 - +131 °F
Storage tempera-
ture
-20 - +75 °C
-4 - +167 °F
Relative humidity
(non-condensing)
80 %
Maximum accelera-
tion (non-operating)
4.0 G
Maximum accelera-
tion (operating)
3.5 G
Protection class (EN
60529)
IP20
Do not expose the PAMIO components to the fol-
lowing conditions:
corrosive gases
high variation of temperature
extremely or salt laden air
metal chip or metal dust - splash water or other
chemicals
NOTICE!
Functional defects!
The PAMIO casing does not provide sufficient pro-
tection against environmental influences. Dust and
moisture may cause malfunctions.
Only operate the PAMIO components inside a
cabinet that ensures at least a protection class
IP 54!
Technical Data
PA 8000 PAMIO
PAMIO Components
12.01.2017 | 51