Page 191                                                                                                             
If P700 = 3 (BS 3680 Weir) 
Select from the following options: 
1 = Rectangular        
2 = V-Notch Full 90 degree  (full 90
o
)            
3 = V-Notch 53 degree 8’ (half 90
o
)                         
4 = V-Notch 28 degree 4’ (quarter 90
o
)                                       
5 = Broad crested (Rectangular) Weir 
If P700 =  4 (Area Velocity) Optional 
The  calculation  of  flow  using  Velocity  Area  is  only  possible  when  the 
optional  current  input  is  available  to  provide  an  input  from  a  velocity 
sensing device which provides a signal proportional to flow. (Please consult 
Pulsar for availability). 
Select from the following options: 
1 = Circular Straight (U-Channel), circular bottom, straight sides.                                                               
2 = Rectangular        
3 = Trapezoidal                                                                    
4 = Round Pipe 
If P700 = 5 (Special) 
Select from the following options: 
1 = Palmer-Bowlus Flume        
2 = H-Flume            
3 = V-Notch angle (other than BS3680) 
If P700 = 6 (Universal) 
Where  the  Primary  Measuring  device  does  not  match  any  of  the  devices 
contained in the above categories then a universal volume calculation can be 
performed. A head Vs flow chart is used, to enter a number of Breakpoints 
for  head  and  flowrate  (P730-793),  which  is  either  provided  by  the 
manufacturer or created based on the dimensions of the device. 
Select from the following options: 
1 = Universal Linear flow calculation    
2 = Universal Curved flow calculation       
3 = Universal Linear Area x Velocity (Optional)         
4 = Universal Curved Area x Velocity (Optional)