Filter (ms): Permits filtering of signals from the safety device. This filter can be set to
between 3 and 250 ms and eliminates any rebounds on the contacts. The duration of the
filter affects calculation of module total response time.
Simultaneity (ms): always active. Determines the maximum permissible time (ms) between
switching of the various signals from the external contacts of the device.
Enable Error Out: If selected reports a fault detected by the function block.
Item description: Permits insertion of a descriptive text of the function of the component.
This text will be displayed in the top part of the symbol.
RESTART INPUT
The element can be used as a digital input
(in addition to the 8 available on MOSAIC M1S (fw>7.0),
MOSAIC M1S COM (fw>7.0), MI8O4 (fw>0.3)) and
connected to any external device.
The usable inputs are referred to RESTART_FBK signals
of MOSAIC M1S (fw>7.0), MOSAIC M1S COM (fw>7.0),
MI8O4 (fw>0.3).
Parameters
Filter (ms): Permits filtering of signals from the external device. This filter can be set to
between 3 and 250 ms and eliminates any rebounds on the contacts. The duration of the
filter affects calculation of module total response time.
FIELDBUS INPUT
Element that permits insertion of a non-safety input
whose status is modified via the fieldbus.
It is possible to insert a maximum of 32 virtual inputs
with MOSAIC M1S/MOSAIC M1S COM and MBx fw >=
2.0, 32 virtual inputs with MOSAIC M1S COM and 8
with MOSAIC M1 or MBx fw < 2.0.
The bit on which status is to be modified must be
selected for each.
On the fieldbus the states are represented with 4
bytes with MOSAIC M1S, MOSAIC M1S COM and 1 byte
with MOSAIC M1.
(For more detailed information, consult the fieldbus manual available in ReeR website).
 WARNING: the FIELDBUS INPUT is NOT a safety input.