MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
94 8540780 • 25/01/2023 • Rev.43
English
MOS8 (Figure 50)
MEANING
LED
REMEDY
RUN
IN FAIL
EXT FAIL
SEL0/1
STATUS1...8
GREEN
RED
RED
ORANGE
YELLOW
Internal fault
OFF
2 / 3 flashes
OFF
Shows the physical
address of the unit
OFF
• Return the unit to ReeR
to be repaired
Compatibility error
OFF
5
flashes
OFF
5
flashes
• Firmware version not
compatible with
MOSAIC M1, return to
ReeR for FW upgrade.
Error in communication
with master
OFF
5
flashes
OFF
OFF
• Restart the system
• If the problem persists,
return the module to
ReeR to be repaired
Error on other
slave or MOSAIC M1
OFF
ON
OFF
OFF
• Restart the system
• Check which unit is in
FAIL mode
Same type of slave with
same address detected
OFF
5
flashes
5
flashes
OFF
• Change the unit's
address
(see NODE SEL)
Error on node detection
circuit
OFF
3 flashes
OFF
3
flashes
OFF
• Return the module to
ReeR to be repaired
Short circuit or overload
detected on status 1-8
output
OFF
OFF
ON
OFF
flash
• Verify output status 1-8
connections
Power supply missing
on status 1-8 output
OFF
OFF
ON
OFF
flash
alternatively
• Connect 5 pin to power
supply
Table 77 - Troubleshooting MOS8
Figure 50 – MOS8

Table of Contents

Other manuals for Reer MOSAIC MI8O4C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Reer MOSAIC MI8O4C and is the answer not in the manual?

Reer MOSAIC MI8O4C Specifications

General IconGeneral
BrandReer
ModelMOSAIC MI8O4C
CategoryController
LanguageEnglish

Related product manuals