MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
8540780 • 25/01/2023 • Rev.43 229
English
CLOCKING
The CLOCKING operator generates a square wave output
which period is set by the user. The output is enabled if
the “En” input is set to 1 (TRUE). Clocking has up to 7
inputs to control output Duty Cycle.
Parameters
Time: The period can be set to between 100 ms and
1098,3 s.
Scale: The user can choose two different scales for the
time T to be set.
100 ms...60 s, step 10 ms
60,1 s...1098,3 s, step 100 ms
Duty cycle selection: Up to 7 inputs can be selected for 7 different output signal duty
cycles. Depending on the active input, the OUT clock signal has its corresponding duty
cycle. EN input must always be to 1 (TRUE).
Refer to the table below for all possible values of Duty cycle selectable by the user.
DUTY CYCLE CHOICE
EN
10%
20%
30%
40%
60%
70%
80%
OUT
0
0
0
0
0
0
0
0
0
1
0
0
0
0
0
0
0
50%
1
1
0
0
0
0
0
0
10%
1
0
1
0
0
0
0
0
20%
1
0
0
1
0
0
0
0
30%
1
0
0
0
1
0
0
0
40%
1
0
0
0
0
1
0
0
60%
1
0
0
0
0
0
1
0
70%
1
0
0
0
0
0
0
1
80%
1
1
0
0
0
0
0
1
90%
The circuit upstream clocking operator must ensure the presence of only one input signal in
addition to enable EN (excluded the pair 10% 80%).
The presence on EN input of high level (TRUE), generates an output signal with a duty cycle = 50%.

Table of Contents

Other manuals for Reer MOSAIC MI8O4C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Reer MOSAIC MI8O4C and is the answer not in the manual?

Reer MOSAIC MI8O4C Specifications

General IconGeneral
BrandReer
ModelMOSAIC MI8O4C
CategoryController
LanguageEnglish

Related product manuals