Rockwell Automation Publication 2099-UM001G-EN-P - December 2022 75
Connect the Kinetix 7000 Drive System Chapter 4
Figure 46 - Impedance-grounded Power Configuration (WYE Secondary)
See Interconnect Diagrams beginning on page 161 for input power interconnect
diagrams.
IMPORTANT
Even though impedance-grounded and corner-grounded power configurations
have a ground connection, treat them as ungrounded when installing
Kinetix 7000 drives.
L1
L2
L3
2099-BM08-S shown with
Lower Front Panel Removed
Transformer (WYE) Secondary
Three-phase
Input VAC
Phase Ground
Transformer
Bonded Cabinet
Ground
Ground Grid or
Power Distribution Ground
To Ground Stud
Line
Filter