Rockwell Automation Publication 1734-UM013J-EN-P - July 2014 117
Configure the Module for a SmartGuard Controller Chapter 6
5. Double-click each Engineering Units Alarms group to display parameters
for editing.
Parameter Name Value Description Default
High High/Low Low Alarm
Enable
Disable Enable or disable alarms.
Disable
Enable
High High Alarm -32768…32767 Follow these guidelines when setting the alarm values.
The High High alarm value must be greater than or equal to the High alarm value.
The High alarm value must be greater that the Low alarm value.
The Low Low alarm value must be less than or equal to the Low alarm value.
These values are based on the Engineering units
32767
Low Low Alarm -32768…32767 0
High Alarm -32768…32767 32767
Low Alarm -32768…32767 0
High High/Low Low Alarm
Deadband
0…32767 Deadband on the High High and Low Low alarms. 0
High/Low Alarm Deadband 0…32767 Deadband on the High and Low alarms. 0