Rockwell Automation Publication 1734-UM013J-EN-P - July 2014 47
Guidelines for Placing Power Supplies and Modules in a System Chapter 3
Example 1: Isolating Field Power Segments
This power supply example uses a 1734-EP24DC expansion power supply and
1734-FPD field power distributor to illustrate mixing standard POINT I/O and
safety POINT Guard I/O modules, while creating separate groups for input and
output modules, as well as digital and analog modules.
Example 2: POINT Guard I/O Used with AC I/O Modules
This power supply example uses 1734-EP24DC and 1734-EPAC expansion
power supplies to illustrate mixing standard POINT I/O and safety POINT
Guard I/O modules, while creating a separate power group for AC I/O modules.
Standard I/O
Standard I/O
Standard I/O
Standard I/O
Standard I/O
Standard I/O
Standard I/O
Standard I/O
Standard I/O
Standard I/O
Standard I/O
Standard I/O
1734-EP24DC
1734-FPD
1734-FPD
1734-EP24DC
1734-AENT
EtherNet/IP Adapter
1734-IB8S
1734-IB8S
1734-OB8S
1734-OB8S
1734-IE4S
1734-IE4S
5V and 24V Supply for
Additional I/O
Modules (option)
5V5V 5V
Group 2 Group 3 Group 4 Group 5Group 1
24V
1734-IB8S
24V Supply for
Safety Outputs
24V Supply for
Safety
Analog Inputs
5V Supply for All Safety
Modules and 24V Supply
for Safety Inputs
5V and 24V Supply for
Standard I/O
Modules
24V24V 24V 24V
Standard I/O
Standard I/O
Standard I/O
Standard I/O
Standard I/O
1734-EPAC
1734-EP24DC
1734-AENT
EtherNet/IP Adapter
Standard I/O
Standard I/O
Standard I/O
Standard I/O
1734-IB8S
1734-IB8S
1734-OB8S
1734-OB8S
1734-IE4S
5V 5V
Group 2Group 1
120V
AC
5V and 120V AC
Supply
5V and 24V Supply for
Safety Inputs and Outputs
5V and 24V Supply
for Standard I/O
Modules
24V
24V
5V
Group 3