Chapter 4 Install the Module
Precautions
Follow these precautions for use.
European Hazardous Location Approval
This equipment is intended for use in potentially explosive atmospheres as 
defined by European Union Directive 94/9/EC and has been found to comply 
with the Essential Health and Safety Requirements relating to the design and 
construction of Category 3 equipment intended for use in Zone 2 potentially 
explosive atmospheres, given in Annex II to this Directive.
Compliance with the Essential Health and Safety Requirements is assured by 
compliance with EN 60079-15 and EN 60079-0.
WARNING: 
• This equipment must be used within its specified ratings as defined by 
Rockwell Automation.
• This equipment must be mounted in an ATEX-certified enclosure with a 
minimum ingress protection rating of at least IP54 ( as defined in IEC 60529) 
and used in an environment of not more than Pollution Degree 2 (as defined in 
IEC 60664-1) when applied in Zone 2 environments.  The enclosure must have a 
tool-removable cover or door.
• Provision shall be made to prevent the rated voltage from being exceeded by 
transient disturbances of more than 140% of the rated voltage when applied in 
Zone 2 environments.
• This device must be used only with ATEX-certified Rockwell Automation 
terminal bases.
• Do not disconnect equipment unless power has been removed or the area is 
known to be nonhazardous.