Configure the Module in a GuardLogix Controller System Chapter 5
The channel offset can be any value from -32768…32767 (engineering 
units) in increments of 1. Configure an offset when differences in the 
sensors nominal input signals would otherwise exceed the desired 
deadband. The channel offset is applied from the second to the first 
member of the channel pair, that is, from channel 1 to channel 0 or from 
channel 3 to channel 2.
6. In the Input Error Latch Time field, enter the time the module holds an 
error to make sure the controller can detect it (0…65,530 ms, in increments 
of 10 ms - default 1000 ms).
This setting provides more reliable diagnostics. The purpose for latching 
input errors is to make sure that intermittent faults that may exist only for a 
few milliseconds are latched long enough to be read by the controller. The 
amount of time to latch the errors should be based on the RPI, the safety 
task watchdog, and other application-specific variables.
7. Click Apply.
Configure the Safety Analog Inputs
Follow these steps to configure the analog input points.
1. From the Module Properties dialog box, click the Input Configuration tab.
2. Assign the Point Mode.
When you click Apply, channel 1 is set to the same value as channel 0 and 
channel 3 is set to the same value as channel 2 if the channel operation is 
configured as dual-channel equivalent.
3. Configure the module for current, voltage, or tachometer inputs.
Choose Description
Not Used The input is disabled.
Safety Safety-related analog input value
Standard Standard analog input value, not being used for a safety function