EasyManuals Logo

Rockwell Automation Allen-Bradley POINT Guard User Manual

Rockwell Automation Allen-Bradley POINT Guard
212 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #191 background imageLoading...
Page #191 background image
Rockwell Automation Publication 1734-UM013J-EN-P - July 2014 191
Appendix F
I/O Assemblies
Input Assemblies
Topic Page
Input Assemblies 191
Output Assemblies 192
Analog Input Assemblies 192
Configuration Assemblies 194
Using Data from Modules Configured via the Generic Profile 200
Table 21 - 1734-IB8S Input Assemblies
Instance
Decimal
(hex)
Connection
Type
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
516 (204h) Safety and
Standard
0 Safety Input
7
Safety Input
6
Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input 1 Safety Input 0
548 (224h) Safety Only 0 Safety Input
7
Safety Input
6
Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input 1 Safety Input 0
1 Safety Input 7 Safety Input
6
Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input 1 Safety Input 0
768 (300h) Standard Only 0 Reserved Input Power
Error
788 (314h) Safety and
Standard
0 Safety Input
7
Safety Input
6
Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input 1 Safety Input 0
1Combined
Safety Input
Reserved Input Power
Error
(1)
Reserved Reserved Reserved Muting Lamp 3 Muting Lamp 1
820 (334h) Safety and
Standard
0 Safety Input
7
Safety Input
6
Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input 1 Safety Input 0
1 Safety Input
7
Safety Input
6
Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input 1 Safety Input 0
2ReservedInput Power
Error
(1)
Reserved Muting Lamp 3 Muting Lamp 1
868 (364h) Safety and
Standard
0 Safety Input 7 Safety Input 6 Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input 1 Safety Input 0
1 Safety Input
7
Safety Input
6
Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input 1 Safety Input 0
2 Reserved Test Output 3 Test Output 2 Test Output 1 Test Output 0
3ReservedInput Power
Error
(1)
Reserved Muting Lamp 3 Muting Lamp 1
899 (383h) Standard 0 Reserved Input Power
Error
1 Reserved Test Output 3 Test Output 2 Test Output 1 Test Output 0
(1) This data is diagnostic only and does not have safety integrity.

Table of Contents

Questions and Answers: