148 Rockwell Automation Publication 1734-UM013J-EN-P - July 2014
Chapter 8 Replacing POINTGuard I/O Modules
6. Verify that the (NS) Network Status indicator is flashing on the correct
module and click OK to set the SNN on that device.
RSNetWorx for DeviceNet software confirms that the SNN has ben set.
Once the download successfully completes, the main project view displays
this message: āThe device at address xx has been downloaded. Any device-
specific messages related to the download operation are displayed
separately.ā
Assuming this is the proper configuration from the original DNT file, the
SNN and configuration signature now match that of the original. If you
are already connected to the controller, a connection is made. The
controller does not need to be taken out of Run mode to download to the
replacement module.