Rockwell Automation Publication 1734-UM013J-EN-P - July 2014 81
Configure the Module in a GuardLogix Controller System Chapter 5
g. From the Input Status pull-down menu, choose from the following
options.
h. From the Data Format pull-down menu, use the default ‘Integer.
Choose Description
None There are no status tags.
Pt. Status There is one status tag for each input point.
Combined Status -
Muting
A single BOOL tag represents an AND of the status bits for all the input
points. For example, if any input channel has a fault, this bit goes LO.
(1)
A single BOOL tag represents the Input Power Status (error bit) from the
input assembly.
A muting status tag for test output T1 and T3.
(1) When using combined status, use explicit messaging to read individual point status for diagnostic purposes.
Pt. Status - Muting There is a muting status tag for test output T1 and T3 with point status for each
input point.
Pt. Status-Muting-Test
Output
Status tags for each of the input points.
Muting status tag for test output T1 and T3.
Status tags for each of the test outputs.