58 Programming SATEL
Bypass on/off the zones belonging to the group will remain bypassed as long as the
bypassing zone is violated (they can be bypassed by the user).
In the LCD keypad, use the BYPASS ON/OFF option to make your selection. Option
disabled see: BYPASS ONLY. Option enabled see: BYPASS ON/OFF.
4.3.9 Groups of partitions
You can define up to 16 partition groups which will be controlled using the 80. ARMING,
81. DISARMING and 83. CLEARING ALARM type zones. The partition groups can be defined:
using the keypad, in the service mode, by means of the GROUPS function (ZONES
GROUPS).
using the DLOADX program, in the Zoneswindow, Arm/Disarm Groupstab.
4.3.10 Zone testing
Using the function available in the service mode menu in the keypad (ZONES TEST), you
can test the zones. Information on violation or tamper of the zone is displayed and signaled
by beeps in keypad (violation 5 short beeps; tamper 1 long beep; masking 3 long
beeps). Additionally, the function allows selection of a system output which will be used for
signaling during the test (zone violation will activate the output for 0.4 second, tamper for
1,6 seconds, masking – for 3 seconds).
Violation/tamper/masking of the zone during the test will not trigger the response
programmed for the control panel zone.
Select a zone for testing from the list and press the or key. The output allocated
for signaling will stop doing its present duty (if it was active, it will be disabled) until the
zone test is completed (the key pressed).
The output used for signaling is only remembered until exiting the TEST function. When
the TEST function is re-started, the output must be selected again.
If wireless sirens are used in the system and any output is selected for signaling, after
selecting a zone for testing from the list and pressing the or key, in the wireless
sirens the signaling will be unblock (which is normally blocked for the service mode
duration).
If the output selected for signaling controls the wireless siren, it should be borne in
mind that the command to block/unblock signaling is sent out during polling. This
results in a delay whose duration depends on the programmed response period. Also
in case of the ASP-205 siren signaling is only triggered during the polling period.
5. Outputs
The system supports the following outputs:
hardwired on the control panel electronics board and in expanders. The number of
available hardwired outputs is determined by the control panel during identification
procedure.
wireless after connecting the ABAX 2 / ABAX wireless system controller. The number of
available wireless outputs depends on the number of wireless devices registered in the
system and is determined during the procedure of adding wireless devices.
virtual the outputs which do not exist physically, but can be used e.g. for execution of
logical functions.
Programming of the outputs is possible:
using the keypad, in the service mode, by means of functions available in the OUTPUTS
submenu,