SATEL INTEGRA Plus 83
For each user schedule, you can:
• program an individual name (up to 16 characters),
• indicate the timers which will determine when the user will have access to the system.
10. Reporting
The control panel can send event codes to the monitoring station using the following
transmission paths:
• analog telephone line,
• Ethernet (connection of the ETHM-1 Plus / ETHM-1 module to the control panel required),
• GPRS (INT-GSM module must be installed in the alarm system or SATEL GSM module
must be connected to the control panel),
• SMS (INT-GSM module is required to be installed in the alarm system) – the control panel
gets no acknowledgement of event code receipt.
The control panel will try to send event code to the monitoring station using in turn:
1. ETHM-1 Plus / ETHM-1 module and/or INT-GSM module. If several such modules are
connected to the control panel, that with the lowest address will be used. Event code can
be sent via Ethernet, GPRS or SMS.
When configuring the ETHM-1 Plus module to which the INT-GSM module is
connected, or when configuring the INT-GSM module connected directly to the control
panel, define priority of the transmission paths. The transmission path which is not
included in the list defining the priority of transmission paths, will not be used.
2. SATEL GSM module for GPRS transmission.
3. analog telephone line (basic and backup telephone number).
If the event code is successfully sent via one transmission path, the other transmission paths
will not be used.
If sending the event code via one transmission path fails, the control panel will try to send the
event code by using the next transmission path. In the case of reporting via the telephone
line, if the event cannot be sent despite completion of the preprogrammed number of retries,
the control panel will hang up until a next event occurs, or for a specified period of time. After
the time expires, the control panel will make further attempts to send the event.
The reporting parameters can be programmed:
• using the keypad, in the service mode, by means of the functions available in the
MONITORING submenu,
• using the DLOADX program, in the “Reporting” window.
For correct operation, the reporting function may require enabling some system options.
Reporting through the ETHM-1 Plus / ETHM-1 / INT-GSM / GSM modules requires that some
telephone options be enabled and settings of these modules properly configured.
Before you proceed to the programming, obtain from the monitoring station operator all data
necessary to correctly start the reporting function:
• depending on the method of sending events:
– telephone number of the monitoring station (telephone reporting),
– server address, port number, STATION KEY and KEY (ETHM) (reporting through Ethernet
network),
– server address, port number, STATION KEY and KEY (GPRS) (GPRS reporting),
– telephone number of the monitoring station and SMS message format (SMS reporting),
• transmission format required by the monitoring station,