86 Programming SATEL
Having selected the CONTACT ID (FULL) or SIA (FULL) format you do not need to
program the assignment of identifiers and any event codes. The control panel will send
the codes according to the format specification and the performed subdivision into
objects.
In the TELIM format, events can only be sent via the analog telephone line.
Telephone
Tel. number [Tel. 1 number] – basic telephone number of the monitoring station.
Backup tel. no. [Tel. 2 number] – a backup telephone number of the monitoring station. The
control panel will make an attempt of reporting to that telephone number, if the attempt of
reporting to the basic telephone number fails.
Backup format [Tel. 2 format] – format in which event codes are sent to the backup
telephone number of the monitoring station.
Repetitions [Repetition count] – the number of attempts to establish telephone connection
with the monitoring station after which, if there is no connection (busy number, no
answer from the station, etc.), the control panel will suspend reporting. Up to 31 retries
can be programmed. Programming the value 0 means that monitoring will be suspended
after 8 attempts.
Suspend time – the time for which telephone reporting is suspended, after making the
programmed number of attempts to establish connection with the monitoring station. The
control panel will resume the attempt of establishing telephone connection with the
monitoring station after this time expires or a next, new event occurs. Up to 30 minutes
can be programmed. Programming the value 0 means that an attempt to establish
telephone connection with the monitoring station will only be taken after occurrence of a
new event in the system.
ETHM/GPRS
Server [IP address] – the address of STAM-2 monitoring station (or SMET-256 converter). It
can be entered in the form of IP address (4 decimal numbers separated by dots) or as a
name.
Port – the number of port through which communication with the monitoring station will be
effected.
Station key [Key (MS)] – the key with which the data sent to the monitoring station will be
encrypted (a string of up to 12 alphanumeric characters). The parameter applies to the IP
SATEL format.
IP format [SIA-IP] – if the event codes are to be sent via Ethernet or GPRS, specify whether
SATEL format or SIA-IP format (SIA DC-09 standard) will be used.
Protocol [UDP] – if the event codes are to be sent via Ethernet or GPRS, specify whether
TCP or UDP protocol will be used.
ETHM key [Key (ETHM)] – the string of up to 5 alphanumeric characters intended to identify
the control panel for the purposes of reporting via Ethernet. The parameter applies to the
IP SATEL format.
GPRS key [Key (GPRS)] – the string of up to 5 alphanumeric characters intended to identify
the control panel for the purposes of reporting using the GPRS technology. The parameter
applies to the IP SATEL format.
It is recommended that the maximum number of characters be programmed for the
keys and that letters, digits and special characters be used, as this will ensure higher
security of the transmission.