Operating instructions Chapter 4
Flexi Classic
8011509/YPP0/2015-10-26 © SICK AG • Industrial Safety Systems • Germany • All rights reserved 79
Subject to change without notice
Special applications and
functions
4.13 ENABLE input
For all UE410-MU- and UE410-XU-devices with a type label entry from E1: In case of single-
channel wiring of a safety capable output (Q1-Q4) to a signal input (EN), it is possible to
achieve category 4 in accordance with EN ISO 13 849-1 or SIL3 in accordance with
IEC 61 508.
The ENABLE input is not available on the UE410-GU.
The ENABLE input makes it possible to cascade safety circuits or to form sub-systems. The
ENABLE input has a higher priority than all other input signals (sensors, muting, bypass,
OR function).
Unused ENABLE inputs must be connected to the supply voltage +U
B
.
When the ENABLE input goes low (0 V DC), the OSSDs (Q1-Q4) always go low and at the
same time no signal such as a reset or muting is detected until ENABLE is high again.
Switching OFF and switching ON ENABLE does not require a renewed reset on the related
modules, the OSSDs (Q1-Q4) go high.
If a time delay has been set on Q3/Q4, the delay starts after the ENABLE input goes low.
Note
Fig.
34
:
ENABLE input
Note
ENABLE function
Q
Start
(switch on and switch off
signal for the start function)
Q
EN
(output of the ENABLE function)
Start-up interlock

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SICK Flexi Classic series and is the answer not in the manual?

SICK Flexi Classic series Specifications

General IconGeneral
BrandSICK
ModelFlexi Classic series
CategoryController
LanguageEnglish

Related product manuals