4.3 Testable single-beam photoelectric safety switches
Testable single-beam photoelectric safety switches can be connected directly to the inputs
of the UE410-MU/UE410-GU/UE410-XU as well as UE410-8DI units.
For category 2 testable photoelectric safety switches (e.g. L21) the response time of the
respective program applies.
For category 4 testable photoelectric safety switches (e.g. L41), the response time is
calculated from the response time of the program plus the test period of the program.
You can find the response times of the programs in chapter 11 “Technical specifica-
tions” on page 96.
The required test signals at X2 for the sensors are generated in program 3.2 of the
UE410-MU/UE410-XU.
The required test signals are generated on X2 in programs 8 and 9 on the UE410-GU.
In switch position 1 of the UE410-8DI the required test signals are generated at outputs
X1 to X8.
Up to 4 testable single-beam photoelectric switches can be cascaded per input. This
means, at the modules UE410-MU/UE410-GU/UE410-XU with one input (I2) each
respectively, at the UE410-8DI with inputs I1 to I8.
A selection of the testable single-beam photoelectric safety switches is available in
section 12.2 “Accessories/spare parts” on page 115.
Ensure protected laying of the connection cables!
If cascades are used, protected separate laying of the connection cables must be ensured.
Connection to UE410-MU/UE410-XU
A testable single-beam photoelectric safety switch/cascade uses the input I2 and test
output X2.
Connection to UE410-GU
A testable single-beam photoelectric safety switch/cascade uses the input I4 and test
output X2.
Connection to UE410-8DI
A testable single-beam photoelectric safety switch/cascade uses the inputs and test
outputs that belong together (for example I1/X1 to I8/X8).
UE410-MU/UE410-XU:
Input I1 and test output X1 have to be jumpered. Terminal S2 may not be
interconnected.
UE410-8DI:
The unused inputs have to be jumpered to the corresponding test outputs (for example
the free inputs I2/X2 to I8/X8).
Notes
WARNING
Note

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SICK Flexi Classic series and is the answer not in the manual?

SICK Flexi Classic series Specifications

General IconGeneral
BrandSICK
ModelFlexi Classic series
CategoryController
LanguageEnglish

Related product manuals