1
Settings for all monitoring cases
2
Settings for a single monitoring case
3
Input conditions for the monitoring case
4
Cut-off paths with the assigned field sets
5
Configured field sets
6
Areas for defined cut-off behavior
7
Remove field set from a monitoring case
Input delay (for all monitoring cases)
In t
he Input delay field, you can set a switch-on delay between 10 and 500 ms. After the
safe multibeam scanner has detected a change in input states, the inputs are ignored
for the duration of the configured switch-on delay.
Monitoring case table
Y
ou can create different monitoring cases in the monitoring case table. You have the
following options for each monitoring case:
Assign the cut-off paths via a field set with fields or using a predefined cut-off
behavior.
Activate sleep mode for the safe multibeam scanner.
Input conditions
T
he input conditions are only displayed if you have created at least two monitoring
cases.
CONFIGURATION 7
8025936/2021-01-08 | SICK O P E R A T I N G I N S T R U C T I O N S | scanGrid2 I/O
55
Subject to change without notice

Table of Contents

Other manuals for SICK scanGrid2 I/O

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SICK scanGrid2 I/O and is the answer not in the manual?

SICK scanGrid2 I/O Specifications

General IconGeneral
BrandSICK
ModelscanGrid2 I/O
CategoryScanner
LanguageEnglish

Related product manuals