Properties and technical specifications of CPU 410 SMART
15.2 Technical specifications of the CPU 410 SMART; (6ES7 410-5HN08-0AB0)
CPU 410-5H Process Automation/CPU 410 SMART
System Manual, 10/2013, A5E32631667-AA
207
6ES7410-5HN08-0AB0
Hardware configuration
connectable OP
119
Multicomputing
No
Number of DP masters
integrated
1
Via IM 467
0
Via CP
0
Number of IO controllers
integrated
1
Via CP
0
Number of usable FMs and CPs (recommendation)
CP, LAN
2
Time
Clock
Hardware clock (real-time clock)
Yes
With battery backup, can be synchronized
Yes
Resolution
1 ms
Deviation per day (with battery backup), max.
1.7 ms; Power Off
Deviation per day (without battery backup), max.
8.6 ms; Power On
Time synchronization
Supported
Yes
On DP, master
Yes
On DP, slave
Yes
On the AS, master
Yes
On the AS, slave
Yes
On Ethernet using NTP
Yes; as client
Time difference in the system with synchronization via
Ethernet, max.
10 ms
Interfaces
Number of RS 485 interfaces
1; PROFIBUS DP
Number of other interfaces
3; 2x Synchronization, 1x Service
PROFINET IO
Number of PROFINET interfaces
1
1. Interface
Type of interface
integrated
Physics
RS 485/PROFIBUS
Electrically isolated
Yes
Power supply at interface (15 to 30 V DC), max.
150 mA
Number of connection resources
32
Functionality
DP master
Yes
DP slave
No

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CPU 410-5H Process Automation and is the answer not in the manual?

Siemens CPU 410-5H Process Automation Specifications

General IconGeneral
BrandSiemens
ModelCPU 410-5H Process Automation
CategoryController
LanguageEnglish

Related product manuals