Communications configuring 
 
3-116  System- and communication configuring D7-SYS - SIMADYN D 
  Edition 12.2003 
Rules: 
•  Communications reference must correspond with that configured with 
CFC (address stage 1 at the address connections). 
•  "MMAZ" is recommended as association type (the subsequent 
information/explanations assume this). 
•  The local LSAP must correspond with the "remote LSAP" of the 
remote communication partner. 
•  The remote address addresses the remote communication partners 
•  Remote LSAP must correspond with the "local LSAP" of the remote 
communications partner. 
•  The maximum PDU length should only be changed if a remote 
communications partner cannot handle the length.  
•  The monitoring interval must correspond with that of the partner. 
•  The multiplier is only relevant for the association type "MSZY" (refer to 
the communication associations). 
•  The Read, Write, Get OV (detailed version), Information report utilities 
and symbolic addressing should be selected as requester (".req") 
and/or responder (".ind"), as they are required. 
−  only select read.req if a receive block uses this association as 
client. 
−  select read.ind if a transmit block is addressed as server via this 
association. 
−  select write.req if a transmit block as client uses this association. 
−  select write.ind if a receive block is addressed as server via this 
association. 
−  information report.req is not used. 
−  select get OV (detailed version) and symbolic addressing if the 
partner supports this utility.  
•  The maximum number of parallel "Transmit" tasks should correspond 
to the number of transmit- and receive blocks configured using CFC 
which also use this communications association (as client). It should 
be observed that for the partner, the maximum number of parallel 
"Receive" tasks should correspond to this minimum number. 
•  The maximum number of parallel "Receive" tasks must be set as high 
as the maximum number of "Transmit" tasks for the partner. 