Communications configuring
3-122 System- and communication configuring D7-SYS - SIMADYN D
Edition 12.2003
Comment:
The communication references must be consecutive (without any
gaps) starting with "2". For instance, if five communication
associations are configured, communication references 2 to 6 should
be used.
"Association type" must be identical for both stations.
The monitoring interval for non-cyclic communication associations
should be the same for both stations.
For servers, the value "255" can be entered for "Remote address" and
"Remote LSAP". In this case, the communications association is
"open", i. e. any client can establish a connection here.
For a client, "Remote address" and "Remote LSAP" must always be
defined; the client then establishes the connection to the specified
partner.
3.7.7.2 Example 2: Process data between three SIMADYN D stations
SIMADYN D notation: Station 1 transmits data to station 2 and sends
data and receives data from station 3.
FMS-notation: Station 1 writes into an object in station 2 and reads
and writes into objects in station 3.
Description