Communications configuring
System- and communication configuring D7-SYS - SIMADYN D 3-317
Edition 12.2003
3.29.8.2 Activating WinCC
In order to establish communications between SIMADYN D and WinCC,
the imported data of the WinCC database must be assigned to the
input/output fields of the graphic configuring software. This is realized by
selecting the appropriate fields in the Graphics Designer and clicking on
the interactive configuration dialog. Each field can be assigned one of the
imported variables. After this assignment has been made, the File menu
item is selected in the main menu, and the data are saved. Before
starting runtime, the connection properties must be set.
Click-on tag management
Click-on SIMADYN D PMC
With the righthand mouse key click-on SD-PMC (CP1613-1)
Click-on properties
Click-on the properties, Channel Unit
Click-on the connection
Enter the Ethernet address for the AG (PLC) (refer to the NML
configuring software)
Receive function : Enter a dedicated TSAP-ID (refer to NML Configuring)
Send function : Enter a dedicated TSAP-ID (refer to NML Configuring)
Confirm with OK
Select "File" in the Control Center
Click-on activate
WinCC is now ready to transfer data between SIMADYN D and WinCC
3.29.8.3 Activating SIMADYN D
Power-up the configured subracks. After the subracks have run-up, the
connection has been established between SIMADYN D and WinCC. Data
is now cyclically transferred between SIMADYN D and WinCC.
In the Control
Center